* What are the reference standards for HV and MV disconnectors specification ? |
The main reference standards, internationally recognized are the ones
published by the IEC (International Electrotechnical Commission):
IEC 60694 : common specifications for HV switchgear and controlgear standards
IEC 62271-102 : Alternating current disconnectors and earthing switches
IEC 60071-1 & 60071-2 : Insulation co-ordination
IEC 60273 : Characteristic of indoor and outdoor post insulators for systems with nominal voltages greater than 1000 V
Tests on indoor and outdoor post insulators of ceramic material or glass for systems with nominal voltages greater than 1000 V
IEC 60815 : Guide for the selection of insulators in respect of polluted conditions
IEC 62271-2 Seismic qualification for rated voltages of 72,5 kv and above
|
* How to understand the notation of Güral HV and MV disconnectors ? |
About High Voltage Disconnectors Notation
Güral Elektrik High Voltage Disconnectors variants are named with abbreviations in the following order.
- Notation
- CBD Center Break Disconnectors.
- TFP Pantograph Disconnectors with double scissors arms.
- TFPK Pantograph Disconnectors with single scissors arms.
- TFPA Pantograph Disconnectors with special single scissors arms for Ur = 245kV only.
- EF Earthing Switches.
- Suffixes I
- None Normal Disconnector or switch.
- E Disconnector with earthing switch, either on load or supply terminals.
- EE Disconnector with two earthing switches, on load and supply terminals.
- Suffixes II
- None 3 phase disconnector.
- e 1 phase disconnector.
- Example 1
- Abbreviation CBDEe 2000
- Explanation Center Break Disconnector with earthing switch, Single phase disconnector at 2000A rated current.
- Example 2
- Abbreviation TFPK 2200
- Explanation Pantograph Disconnector with single scissors arms, 3 phase disconnector at 2200A rated current.
About Medium Voltage Disconnectors Notation
Güral Elektrik Medium Voltage Disconnectors variants are named with abbreviations in the following order.
Rocking disconnectors
- Notation
- H: Outdoor, single or three phases,
- D: Indoor , single or three phases,
- A: Normal.
- T: Integrated with one earthing switch.
- TT: Integrated with two earthing switches.
- S: Integrated with fuse-base .
Centre break disconnectors
- Notation
- CBD: Centre break , three phases
- CBDe: Centre break , single phase,
- CBDE: Centre break, three phase, integrated with one side earthing switch .
- CBDEe: Centre break, single phase, integrated with one side earthing switch .
- CBDEE: Centre break, three phase, integrated with two sides earthing switch.
- CBDEEe: Centre break, single phase, integrated with two sides earthing switch.
Double break disconnectors
- Notation
- DBD: Double break , three phases
- DBDe: Double break , single phase,
- DBDE: Double break, three phase, integrated with one side earthing switch .
- DBDEe: Double break, single phase, integrated with one side earthing switch .
- DBDEE: Double break, three phase, integrated with two sides earthing switch.
- DBDEEe: Double break, single phase, integrated with two sides earthing switch.
Earthing switches
- Notation
- H: Outdoor, single or three phases,
- D: Indoor , single or three phases,
- TA: Earthing switch.
Quick make earthing switches
- Notation
- H: Outdoor, single or three phases,
- D: Indoor , single or three phases,
- TA: Earthing switch,
- Y: Integrated with quick make mechanism.
|
|
What are the reference standards for DC disconnectors specification ? |
The main reference standards, internationally recognized are the ones published by the IEC (International Electrotechnical Commission):
IEC 61992-1 : DC switchgear; General,
IEC 61992-3 : DC switchgear; Indoor d.c. disconnectors , switch-disconnectors and earthing switches,
IEC 61992-4 : DC switchgear; Outdoor d.c. disconnectors, switch-disconnectors and earthing switches,
|
How to understand the notation of Güral DC disconnectors ? |
Güral Elektrik DC (direct current) Disconnectors variants are named with abbreviations in the following order.
- Notation
- DCN: Outdoor, without earthing switch,
- DCE: Outdoor, integrated with one side earthing switch
- DCEE: Outdoor, integrated with two sides earthing switches ,
|
|
What are the reference standards for Switch-Disconnectors and Switch-Fuse Combinations specification ? |
The main reference standards, internationally recognized are the ones published by the IEC (International Electrotechnical Commission): IEC 60265-1 : Switches for rated voltages above 1kV and less than 52kV,
IEC 62271-105 : Alternating current switch-fuse combinations,
IEC 62271-102 : Alternating current disconnectors and earthing switches.
|
How to understand the notation of Switch-Disconnectors and Switch-Fuse Combinations ? |
Güral Elektrik Switch- Disconnectors and Switch-Fuse Combinations variants are named with abbreviations in the following order.
Outdoor Switch-Disconnectors and Switch-Fuse Combinations
- Notation
- H: Outdoor,
- A: Normal ,
- Y: On-Load,
- S: With fuse-base,
- K: With breaking whip,
- T: With earthing switch
- Example 1
- Abbreviation HAY
- Explanation Outdoor type, normal switch-disconnector.
- Example 2
- Abbreviation HAKY
- Explanation Outdoor type, normal switch-disconnector with breaking whip.
Indoor Switch-Disconnectors and Switch-Fuse Combinations
- Notation
- SD: Indoor , without earthing switch,
- SDE: Indoor, integrated with one earthing switch ,
- SFC: Indoor , Switch-Fuse Combination,
- SFCE: Indoor, Switch-Fuse Combination integrated with one earthing switch ,
|
|
What are the reference standards for HV fuses and fuse mountings specification ? |
The main reference standards, internationally recognized are the ones published by the IEC (International Electrotechnical Commission):
IEC 60282-1 : High-voltage fuses- current limiting fuses,
IEC 60787 : Application guide for the selection of high-voltage current- limiting fuse-links for transformer circuits ,
IEC 60644 : Specification for high-voltage fuse-links for motor circuit applications
IEC 60549 : High-voltage fuses for the external protection of shunt power capacitors
|
How to understand the notation of Güral HV fuses and fuse mountings ? |
Güral Elektrik HV current-limiting fuses and fuse mountings variants are named with abbreviations in the following order.
HV current-limiting fuses,
- Notation
- MGN: Outdoor, without striker,
- MGM: Outdoor, with striker
Fuse mountings,
- Notation
- H: Outdoor,
- D: Indoor
- SA: Fuse-base
- Example
- Abbreviation DSA
- Explanation Indoor type fuse-base
|
|
What are the reference standards for Live Working Equipment specification ? |
The main reference standards, internationally recognized are the ones published by the IEC (International Electrotechnical Commission):
IEC 61111 : Matting of insulating material for electrical purposes ,
IEC 60832 : Insulating poles (insulating sticks) and universal tool attachments (fittings) for live working ,
IEC 61243-1 : Live working - Voltage detectors - Part 1: Capacitive type to be used for voltages exceeding 1 kV a.c.
IEC 61243-2 : Live working - Voltage detectors - Part 2: Resistive type to be used for voltages of 1 kV to 36 kV a.c. |
|
|
|
| |
|
|
 |
| WORKSHOP |
Atatürk Sanayi Sitesi, Fahri Korutürk Caddesi, 323 Sokak, No:1, 34900
Hadımköy – ISTANBUL / TURKEY |
Tel: +90 212 771 24 95-99 / 771 27 60-61 Fax: +90 212 771 27 62 |
|
| OFFICE |
Rıhtım Cadddesi, C Blok, No:59, Kat:2, Daire: 25, 34425
Karaköy – ISTANBUL / TURKEY |
|
Tel: +90 212 249 82 80 Fax: +90 212 244 25 07 |
|
|
 |
| |
| |
|
| copyright © 2007 Güral Elektrik Malzemeleri Ticaret ve Sanayi A.Ş. |
| Project By |
 |
|
|
|
 |
|
 |
|
|