DISCONNECTORS
 HV Disconnectors
 Centre Break
 Pantograph
 Horizontal Break Pantograph
 (knee type)
 Earthing Switches
 Operating Mechanisms
 MV Disconnectors
 Indoor Rocking
 Outdoor Rocking
 Centre Break
 Double Break
 Indoor Earthing Switches
 Outdoor Earthing Switches
 Quick Make Earthing Switches
 Operating Mechanisms
 DC Disconnectors
 for Railway Applications
 Operating Mechanisms
 Switch-Disconnectors
 Outdoor Switch-Disconnectors
 Indoor Switch-Disconnectors
 Operating Mechanisms
 Switch Disconnectors
 Fuse Combinations
 Indoor Switch Disconnector
 Fuse Combinations
 Operating Mechanisms
 HV FUSES
 Current Limiting Back-up Fuses
Indoor Fuse Bases  
Outdoor Fuse Bases
 LIVE WORKING
 Voltage Detectors
 Insulating Sticks
 Rescue Sticks
 Fuse Handle
 Insulating Mats



  

General

Güral introduces air insulated HAY/ HTYSeries Outdoor Switch-Disconnectors of normal, with earthing blade types and HAKY/ HTKYSeries Outdoor Switch-Disconnectors with Breaking Whip of normal, with earthing blade types : a solid and compact solution for medium voltage systems. The design combines leading compactness of its class with maximum electrical and mechanical endurances as described in the relevant standards.

For many years Güral outdoor switch-disconnectors have guaranteed an excellent position in switchgear engineering. These switch-disconnectors master the daily loads exerted under normal switching duty - for interrupting ring feeders, disconnecting network transformers and such - with very high operating frequencies and a minimum amount of maintenance. These switch-disconnectors are distinguished by simple design, absolute reliability in operation and easy actuation.

The HAY/ HTY Series outdoor switch-disconnectors are fitted with an arc extinguishing chamber and HAKY/ HTKY Series outdoor switch-disconnectors are fitted with a breaking whip.

Güral Outdoor Switch Disconnectors offer robust and reliable solutions for medium – voltage systems. The 1-, 2- and 3-pole Outdoor switch- disconnectors are applicable for a wide range system voltages from 12 kV to 36 kV and a rated current range from 400 A to 630 A. The rated short time current is up to 25 kA for a duration of 1 s depending on the model has been tested.

The flexibility of the design of Güral MV Outdoor switch disconnectors allows almost any custom solutions requested by the client.

Base and Shaft

MV Outdoor switch disconnector consists of single, two or three poles with or without earthing switches. Single, two and three poles switch disconnectors consistof a base, a number of fixed support insulators depending on type of switch disconnector, one/two/three operating insulators depending on number of phases, a main shaft, an earthing shaft for earthing switch and one/two/three main blades depending on number of phases that moves in a vertical plane. All steel parts of the disconnector are hot-dip galvanized.

Insulators


The switch disconnector can be equipped with insulators in accordance with IEC, ANSI or DIN specifications.

Current carrying part


The twin sectioning blades and terminals are made of electrolytic copper. Terminals and contact surfaces of blades are silver plated.

The twin sectioning blades are pressed on terminal contacts by means of a number of spiral springs depending on required contact pressure due to short-circuit capability, ensure that the current is transferred from the terminal contacts into twin sectioning blades. This blade and contact construction is maintenance free.

The contacts are self-cleaning, which makes the switch disconnector suitable for installation in all areas with severe climatic conditions.

Arc extinguishing chamber NPAK5 for switch-disconnectors up to 24kV and types HAY/ HTY


The fault (short-circuit or earth fault) shall be cleared by a circuit breaker before opening switch disconnectors.

HAY/ HTY switch-disconnectors can be closed against fault if the specified short-circuit making current is not exceeded.

Breaking chamber NPAK5 has an internal spring device and the making capacity is independent of the operating speed.

Arc extinguishing chamber L2 for 36kV switch-disconnectors types HAY/ HTY

Arc exitinguishing chamber L2 is only used for breaking the currents up to 400A.

Breaking whip for switch-disconnectors types HAKY/ HTKY

A simple disconnector can be fitted with breaking whips to have the breaking capacity. The disconnectors are always fitted with breaking whips to safely break the load currents.

Earthing switch

Güral MV Outdoor switch disconnectors may be equipped with earthing switches. An interlocking between the main and earthing shaft is available. The interlock prevents earthing the disconnector closed or vice versa.

Operating mechanism

The switch disconnectors can be single, two or three poles operated by means of a motor-operated drive mechanism or a manual-operated drive mechanism.

Güral Outdoor switch disconnector can be drived by any controlgear model designed by Güral; drive model is to be decided according to application requirements.

Testing

MV Outdoor switch disconnectors are designed and tested in accordance with latest IEC standards.

Installation

MV Outdoor switch disconnectors are completely assembled and adjusted in our workshops. Its design permits both vertical and horizontal mounting.

The construction is designed so that all outdoor switch disconnectors can be installed at site very easily, without the need of any special tools. For each switchgear an instruction manual for transportation, mounting and commissioning is enclosed. This instruction manual should be strictly followed.

Maintenance

The MV Outdoor switch disconnectors supplied by Güral are designed so as to ensure that they are maintenance free.

However, to guarantee a long and trouble-free service period, we advise that a visual inspection of the contacts and bearing points be carried out at regular intervals.

Superiorities of Güral Outdoor switch disconnectors

  • Designed to permit both vertical and horizontal mounting.
  • The main moving blades and terminals are made of electrolytic copper .
  • Terminals and contact surfaces of blades are silver plated.
  • The framework is hot deep galvanised.
  • From the simplest of manually operated units to motorized and automated remotely controlled units.
  • Wide range of accessories.
  • High quality silicone or porcelain insulators.
  • Light weight design with a limited number of parts guarantees a long lifetime and trouble-free
    operation.


Technical data for types HAY/HTY


Rated Voltage

Ur(kV)

12

17.5

24

36

Power Frequeny Withstand Voltage

 

- to earth and between phases   

Ud(kV)

28

38

50

70

- across isolating distance              

Ud(kV)

32

45

60

80

Lightning Impulse Withstand Voltage

 

- to earth and between phases       

Up(kV)

75

95

125

170

- across isolating distance              

Up(kV)

85

110

145

195

Rated Current                               

Ir(A)

630

400

400

400

Rated Short-time Withstand Current

Ik(kA)

20

20

20

20

Rated Peak Withstand Current

Ip(kA)

50

50

50

50

Rated Short-circuit Making Current

Ima

12.5

10

10

10

Rated Mainly Active Load Breaking Current

A

630

630

630

400

Rated Closed-loop Load Breaking Current

A

630

400

400

400

Rated No-load Transformer Breaking Current

A

2

2

2

2

Rated Cable-charging Breaking Current

A

10

10

10

16

Rated Earth-fault Breaking Current

A

50

50

50

50

Mechanical operations

nos

1000

1000

1000

1000

Class

 

E3

E1

E1

E1



Technical data for types HAKY/HTKY




Rated Voltage

Ur(kV)

12

17.5

24

36

Power Frequeny Withstand Voltage

 

- to earth and between phases       

Ud(kV)

28

38

50

70

- across isolating distance              

Ud(kV)

32

45

60

80

Lightning Impulse Withstand Voltage

 

- to earth and between phases       

Up(kV)

75

95

125

170

- across isolating distance              

Up(kV)

85

110

145

195

Rated Current                                

Ir(A)

630

630

630

630

Rated Short-time Withstand Current

Ik(kA)

20

20

20

20

Rated Peak Withstand Current

Ip(kA)

50

50

50

50

Rated Mainly Active Load Breaking Current

A

16

16

16

16

Rated Closed-loop Load Breaking Current

A

16

16

16

16

Rated No-load Transformer Breaking Current

A

2

2

2

2

Rated Cable-charging Breaking Current

A

10

10

10

10

Rated Earth-fault Breaking Current

A

20

20

20

20

Mechanical operations

nos

1000

1000

1000

1000

Class

 

E3

E3

E3

E3


Dimensions (mm) :
Dimensions having (*) is changing acc.to client’s specifications
  

 


OUTDOOR SWITCH-DISCONNECTORS TYPES HAY/HTY


  

 

Dimensions  (mm)

Type 

A

B(*)

C

D

E

F

L(*)

HAY12

630

500

640

890

1130

850

1680

HAY17.5

700

550

680

950

1230

920

1780

HAY24

800

600

730

1000

1330

1020

1880

HAY36

900

700

870

1200

1530

1120

2080

HTY12

630

500

640

890

1130

900

1680

HTY17.5

700

550

680

950

1230

970

1780

HTY24

800

600

730

1000

1330

1070

1880

HTY36

900

700

870

1000

1530

1170

2080






 

OUTDOOR SWITCH-DISCONNECTORS TYPES HAKY/HTKY



 

Dimensions  (mm)

Type 

A

B(*)

C

D

E

F

L(*)

HAKY12

430

380

940

980

926

690

1140

HAKY17.5

540

380

980

1020

926

800

1140

HAKY24

585

420

1030

1070

1006

845

1250

HAKY36

630

490

1170

1210

1146

890

1580

HTKY12

430

380

940

980

926

740

1140

HTKY17.5

540

380

980

1020

926

850

1140

HTKY24

585

420

1030

1070

1006

895

1250

HTKY36

630

490

1170

1210

1146

940

1580

 


 
   
WORKSHOP
Atatürk Sanayi Sitesi, Fahri Korutürk Caddesi, 323 Sokak, No:1, 34900
Hadımköy – ISTANBUL / TURKEY
Tel: +90 212 771 24 95-99 / 771 27 60-61     Fax: +90 212 771 27 62
OFFICE
Rıhtım Cadddesi, C Blok, No:59, Kat:2, Daire: 25, 34425
Karaköy – ISTANBUL / TURKEY
Tel: +90 212 249 82 80      Fax: +90 212 244 25 07
 
 
copyright © 2007 Güral Elektrik Malzemeleri Ticaret ve Sanayi A.Ş.
Project By
 
ss